    Features
  • Combustible at a low flow rate & pressure Secure combustion with
    CH4 60% / CO2 40%
    Supply pressure: 2kPa~
  • No need of power source
  • As flare stack for biogas device
  • No need of additional fuel

Standard specification

* Please note that product specifications are subject to change without notice.
Burner designation type S type 1 type 2 type 3
Capacity Nm³/h 12.5 25 50 75
Flammable gas percentage % 60
Inert gas percentage % 40
Pressure at device kPa 2
Burner designation 125CH
Quantity of burner 1 1 2 3
Device height mm 3,680 4,720 4,890 5,020
Combustion sleeve outside diameter φmm 550 800 1,100 1,400
Combustion sleeve height mm 2,600 3,500
Hood dimensions mm φ900×280H φ1,300×420H φ1,800×590H φ2,300×720H
Frame dimensions mm □950×800H □1,200×800H □1,500×800H □1,800×800H
Ignition system Spark rod
Batch Lighting
Frame detection UV detector
Quantity 1
Combustion volume control method Non adjusting flow by limiting valve
Safety device-1 Exhaust gas excess temperature
Safety device-2 Disposal gas pressure drop
Observation port Existence
Power Single phase AC 200V 1kVA Single phase AC200V 1.5kVA
Control panel dimensions mm W500×D200×H630
Insulate plate Existence
* Please note that product specifications are subject to change without notice.
Burner designation type 4 type 5 type 6
Capacity Nm³/h 100 125 150
Flammable gas percentage % 60
Inert gas percentage % 40
Pressure at device kPa 2
Burner designation 125CH
Quantity of burner 4 5 6
Device height mm 5,280 5,410 5,440
Combustion sleeve outside diameter φmm 1,600 1,800 1,900
Combustion sleeve height mm 3,500
Hood dimensions mm φ2,600×780H φ2,900×910H φ3,050×940H
Frame dimensions mm □2,000×1,000H □2,200×1,000H □2,300×1,000H
Ignition system Spark rod
Batch Lighting
Frame detection UV detector
Quantity 1
Combustion volume control method Non adjusting flow by limiting valve
Safety device-1 Exhaust gas excess temperature
Safety device-2 Disposal gas pressure drop
Observation port Existence
Power Single phase AC200V 2.0kVA
Control panel dimensions mm W500×D200×H630
Insulate plate Existence

External Dimension・Data Flow Diagram

【type1 External Dimension】
【type1 Data Flow Diagram】
type S External Dimension.PDF Data Flow Diagram.PDF
type 1 External Dimension.PDF Data Flow Diagram.PDF
type 2 External Dimension.PDF Data Flow Diagram.PDF
type 3 External Dimension.PDF Data Flow Diagram.PDF
type 4 External Dimension.PDF Data Flow Diagram.PDF
type 5 External Dimension.PDF Data Flow Diagram.PDF
type 6 External Dimension.PDF Data Flow Diagram.PDF
ページ先頭へ